WBIO-DO-R1G-16 1A Relay Module/en: различия между версиями
(Новая страница: «{| class="wikitable" !Parameter !Value |- |Number of outputs |16 |- |Number of output groups |2 |- |Output type |mechanical relay |- |Contact configuration |SPST,…») |
FuzzyBot (обсуждение | вклад) (Часть переводимой страницы WBIO-DO-R1G-16 I/O Module.) |
||
(не показано 11 промежуточных версий 2 участников) | |||
Строка 35: | Строка 35: | ||
states: | states: | ||
* | *off. | ||
* | *Kx and NO closed | ||
|- | |- | ||
| | |Maximum switching voltage, alternating current | ||
|250 | |250 V | ||
|- | |- | ||
| | |Maximum switching voltage, direct current | ||
|30 | |30 Volts | ||
|- | |- | ||
| | |Maximum switching current, per channel (*) | ||
|5 | |5 A | ||
|- | |- | ||
| | |Maximum switching current, | ||
the channels in one group | |||
|10 | |10 A | ||
|- | |- | ||
| | |The channel resistance in the open state | ||
|< 50 | |< 50 mW | ||
|- | |- | ||
| | |Voltage isolation between the controller and the output | ||
|2000 | |2000 V (RMS.) | ||
|- | |- | ||
| | |Lifetime: number of switches | ||
for load 3 A 230 V AC, cos φ = 1 | |||
|100 000 | |100 000 | ||
|- | |- | ||
| | |Lifetime: number of switches | ||
for load 0.1 A 230 V AC, cos φ = 1 (**) | |||
|1 000 000 | |1 000 000 | ||
|- | |- | ||
| | |Module type | ||
|"O" (non-inverted address scheme) | |"O" (non-inverted address scheme) | ||
|- | |- | ||
| | |Maximum power consumption | ||
|1 | |1 W | ||
|- | |- | ||
| | |Width, DIN units | ||
|3 | |3 | ||
|- | |- | ||
| | |Size | ||
|53,3x90,2x57,5 | |53,3x90,2x57,5 mm | ||
|} | |} | ||
<nowiki>*</nowiki>) | <nowiki>*</nowiki>) Maximum switching current is specified for 230 VAC resistive load. | ||
<nowiki>**</nowiki>) | <nowiki>**</nowiki>) Calculated value | ||
{| class="wikitable" | {| class="wikitable" | ||
!colspan="2" | ''' | !colspan="2" | '''Terminals and wire section''' | ||
|- | |- | ||
|| | || The recommended wire cross section with pin bushing insulated tip, mm<sup>2</sup> || 2,5 | ||
|- | |- | ||
|| | || Standard sleeve length of pin bushing insulated tip, mm || 8 | ||
|- | |- | ||
|| | ||Tightening torque of screws, Н∙м || 0,5 | ||
|- | |- | ||
|} | |} | ||
[[File:DIN 3U.png |300px|thumb|right| | [[File:DIN 3U.png |300px|thumb|right|Dimensions]] | ||
== | == Connection to the controller == | ||
See [[Модули ввода-вывода/en#Activating the modules in the controller web interface|Activating the modules in the web interface of the controller]] | |||
== | == Load connection== | ||
Relays are connected in a phase break. | |||
[[Файл:Relay outputs.png|400px|thumb|none| | [[Файл:Relay outputs.png|400px|thumb|none|Connection scheme]] | ||
== Device pictures and drawings == | |||
== | |||
{{Wbincludes:WBPictures|1}} | {{Wbincludes:WBPictures|1}} |
Текущая версия на 13:02, 22 апреля 2021
Purpose
Control of contactors, warning lights, etc.
Technical specifications
Contains 16 HF49FD relays [(Datasheet)] with the configuration of contacts SPST (two contacts on the relay: NO/COM).
The relays are combined into two groups of 8 pieces, each group has one common COM pin: the upper COM pin for relays K1 — K8 and the lower COM pin for relays K9 — K16. There's no connection between groups, so the first group can switch one voltage source, and the second - the other.
Rated channel current: 1 A. The module has protection against sparking of the contacts.
Our detailed article in russian on habr.com about the choice of relay parameters for the switched load: https://habr.com/ru/company/wirenboard/blog/422197/
Parameter | Value |
---|---|
Number of outputs | 16 |
Number of output groups | 2 |
Output type | mechanical relay |
Contact configuration | SPST, normally open
states:
|
Maximum switching voltage, alternating current | 250 V |
Maximum switching voltage, direct current | 30 Volts |
Maximum switching current, per channel (*) | 5 A |
Maximum switching current,
the channels in one group |
10 A |
The channel resistance in the open state | < 50 mW |
Voltage isolation between the controller and the output | 2000 V (RMS.) |
Lifetime: number of switches
for load 3 A 230 V AC, cos φ = 1 |
100 000 |
Lifetime: number of switches
for load 0.1 A 230 V AC, cos φ = 1 (**) |
1 000 000 |
Module type | "O" (non-inverted address scheme) |
Maximum power consumption | 1 W |
Width, DIN units | 3 |
Size | 53,3x90,2x57,5 mm |
*) Maximum switching current is specified for 230 VAC resistive load.
**) Calculated value
Terminals and wire section | |
---|---|
The recommended wire cross section with pin bushing insulated tip, mm2 | 2,5 |
Standard sleeve length of pin bushing insulated tip, mm | 8 |
Tightening torque of screws, Н∙м | 0,5 |
Connection to the controller
See Activating the modules in the web interface of the controller
Load connection
Relays are connected in a phase break.
Device pictures and drawings
По ссылкам ниже вы можете скачать изображения и чертежи устройства WBIO-DO-R1G-16.
Corel Draw 2018: WBIO-DO-R1G-16.cdr.zip
Corel Draw PDF: WBIO-DO-R1G-16.cdr.pdf
Autocad 2013 DXF: WBIO-DO-R1G-16.dxf.zip
Autocad PDF: WBIO-DO-R1G-16.pdf