Relay Module Modbus Management/en: различия между версиями
(Новая страница: «The Wirenboard relay modules support all major Modbus commands. Read more here: Протокол_Modbus/en#Register reading and writing function codes|Register…») |
(Новая страница: «=== Safe mode === In this mode, when the Modbus communication is terminated, the device disconnects the relay after a specified time.») |
||
Строка 12: | Строка 12: | ||
The Wirenboard relay modules support all major Modbus commands. Read more here: [[Протокол_Modbus/en#Register reading and writing function codes|Register reading and writing function codes]]. | The Wirenboard relay modules support all major Modbus commands. Read more here: [[Протокол_Modbus/en#Register reading and writing function codes|Register reading and writing function codes]]. | ||
=== | === Safe mode === | ||
In this mode, when the Modbus communication is terminated, the device disconnects the relay after a specified time. | |||
Для включения безопасного режима (Safety timer) нужно записать значение, отличное от 0, в регистр хранения командой WRITE_SINGLE_REGISTER по адресу 8. Это значение — таймаут в секундах. Значение "0" отключает безопасный режим. | Для включения безопасного режима (Safety timer) нужно записать значение, отличное от 0, в регистр хранения командой WRITE_SINGLE_REGISTER по адресу 8. Это значение — таймаут в секундах. Значение "0" отключает безопасный режим. |