See [[Модули ввода-вывода/en#Activating the modules in the controller web interface|Activating the modules in the web interface of the controller]]. In the Discrete I/O device, EXT(1-8)_DIR(1-4) and EXT(1-8)_ON(1-4) controls will be created after the module connection. DIR controls are responsible for direction selection (relay R2 on the circuit), and ON controls are responsible for switching on and off (relay R1 on the circuit). These controls in MQTT messages are called /devices/wb-gpio/controls/EXT'''x'''_DIR'''y''' and /devices/wb-gpio/controls/EXT'''x'''_ON'''y'''. | See [[Модули ввода-вывода/en#Activating the modules in the controller web interface|Activating the modules in the web interface of the controller]]. In the Discrete I/O device, EXT(1-8)_DIR(1-4) and EXT(1-8)_ON(1-4) controls will be created after the module connection. DIR controls are responsible for direction selection (relay R2 on the circuit), and ON controls are responsible for switching on and off (relay R1 on the circuit). These controls in MQTT messages are called /devices/wb-gpio/controls/EXT'''x'''_DIR'''y''' and /devices/wb-gpio/controls/EXT'''x'''_ON'''y'''. | ||
[[File:WBIO-DO-R10R-4-controls.png|300px|thumb|right| | [[File:WBIO-DO-R10R-4-controls.png|300px|thumb|right|Module's controls in the web interface]] | ||
== Выходы модуля — подключение нагрузки== | == Выходы модуля — подключение нагрузки== |
Версия 14:55, 15 июля 2019
Purpose
Control of electric curtains, shutters, shutoff valves.
Technical specifications
Contains 4 relay groups.
Each group has three possible states.
Parameter | Value |
---|---|
Number of output groups | 4 |
Output type | mechanical relay |
Contact configuration | SPCO/all sptt (see scheme)
output group states:
|
Maximum switching voltage, AC | 250 V |
Maximum switching voltage, DC | 30 Volts |
Maximum switching current, per channel (*) | 3 A |
The channel resistance in the open state | < 100 mOhm |
Voltage isolation between the controller and the output | 1500 V (RMS.) |
Lifetime: number of switches
for 10 A 230 V AC load, cos φ = 1 |
100 000 |
Module type | "O" (non-inverted address scheme) |
Maximum power consumption | 1 W |
Width, DIN units | 3 |
Size | 53,3x90,2x57,5 mm |
*) Maximum switching current is specified for 230 VAC resistive load.
Terminals and wire section | |
---|---|
The recommended wire cross section with pin bushing insulated tip, mm2 | 2,5 |
Standard sleeve length of pin bushing insulated tip, mm | 8 |
Tightening torque of screws, Н∙м | 0,5 |
Connection to the controller
Connection to the controller
See Activating the modules in the web interface of the controller. In the Discrete I/O device, EXT(1-8)_DIR(1-4) and EXT(1-8)_ON(1-4) controls will be created after the module connection. DIR controls are responsible for direction selection (relay R2 on the circuit), and ON controls are responsible for switching on and off (relay R1 on the circuit). These controls in MQTT messages are called /devices/wb-gpio/controls/EXTx_DIRy and /devices/wb-gpio/controls/EXTx_ONy.
Выходы модуля — подключение нагрузки
Фазный провод подключается к клеммам Lx. Обе клеммы группы контактов Lx соединены на плате. Клеммы NC и NO подключаются к двигателю, задавая направление вращения. Выходы NO и NC защищены варисторами.