WBIO-DI-HVD-8 8-Channel 230V Detector Module/en: различия между версиями
(Новая страница: «== Connection ==») |
(Новая страница: «The inputs are divided into two isolated terminal groups: (1,2,3,4,N) and (N,5,6,7,8) -- in version 1 and (1,2,3,4,N,N) and (N, N,5,6,7,8) -- version 2. N - commo…») |
||
Строка 73: | Строка 73: | ||
== Connection == | == Connection == | ||
The inputs are divided into two isolated terminal groups: | |||
(1,2,3,4,N) | (1,2,3,4,N) and (N,5,6,7,8) -- in version 1 and (1,2,3,4,N,N) and (N, N,5,6,7,8) -- version 2. N - common zero for a group of inputs. | ||
[[Файл:AC Det.png|400px|thumb|none|Схема подключения модуля WBIO-DI-HVD]] | [[Файл:AC Det.png|400px|thumb|none|Схема подключения модуля WBIO-DI-HVD]] |
Версия 15:07, 15 июля 2019
Purpose
Control of contactors, circuit integrity, etc.
Technical specifications
Contains 8 inputs to determine the presence of 220V. The operating voltage of the inputs is 50V-250V AC.
Parameter | Value |
---|---|
Number of inputs | 8 |
Isolated input groups | 2 |
Input type | voltage input |
Operating voltage | 50V AC |
Rated voltage | 230V AC |
Response time (230V AC), not more than | 100 ms |
Isolation voltage between input and controller | 5000Vrms |
Module type | I (inverted addr.) |
Maximum power consumption | 1 mW |
Width, DIN units | 2 |
Size | 36,3x90,2x57,5 mm |
Terminals and wire section | |
---|---|
The recommended wire cross section with pin bushing insulated tip, mm2 | 2,5 |
Standard sleeve length of pin bushing insulated tip, mm | 8 |
Tightening torque of screws, Н∙м | 0,5 |
Connection to the controller
See Activating the modules in the web interface of the controller
Connection
The inputs are divided into two isolated terminal groups: (1,2,3,4,N) and (N,5,6,7,8) -- in version 1 and (1,2,3,4,N,N) and (N, N,5,6,7,8) -- version 2. N - common zero for a group of inputs.
Изображения и чертежи устройства
По ссылкам ниже вы можете скачать изображения и чертежи устройства WBIO-DI-HVD-8.
Corel Draw 2018: WBIO-DI-HVD-8.cdr.zip
Corel Draw PDF: WBIO-DI-HVD-8.cdr.pdf
Autocad 2013 DXF: Мы еще не подготовили чертеж этого устройства. Вы можете запросить чертеж устройства "the 220V voltage presence detection module WBIO-DI-HVD-8" на портале техподдержки Wiren Board (необходима регистрация).