WBIO-DI-DR-8 I/O Module
Шаблон:DisplayTitle: Discrete inputs dry contact module (WBIO-DI-DR-8)
Applicability
Connection of pulse counters, buttons, switches, sensors with dry contact output.
Technical specifications
Contains 8 dry contacts inputs with group galvanic isolation. The scheme of inputs is shown in the figure. The terminal is supplied by ~ 4.5 V voltage, when the ground fault,flows a small (1mA) current, causing the operation of the input.
Parameter | Value |
---|---|
Number of inputs | 8 |
Isolated input groups | 1 |
Input type | dry contact,
the opening by the current at ground fault |
Operation condition | GND input lockout |
Tripping current | 1 mA |
Minimum pulse width to trigger | 10 MS |
Minimum time between consecutive signals | 5 MS |
Voltage of "wetting" | 4.5 V |
Module type | "I" (inverted address scheme) |
Maximum power consumption | 0.1 W |
Width, DIN units | 2 |
Size | 36,3x90,2x57,5 mm |
"'Terminals and wire section'" | |
---|---|
Recommended wire cross-section with TSVI, mm2 | 0,75 — 1 |
Length of the standard sleeve NSVE, mm | 8 (10 for adjusting screwless terminal blocks) |
Torque of screws, N∙m | 0,2 (for screw terminals) |
Connection to the controller
See Activating the modules in the web interface of the controller
Connection
Sensors/counters with pulse outputs/buttons.
Such devices form a signal by closing two wires that are suitable for them. Connect one wire to the GND terminal of the module. Connect the second wire to the Dx terminal. Some counters have a pulse output on the optocoupler, then the two wires have a polarity - "plus" and "minus". In this case, minus is connected to GND, plus - to Dx.
Устройства с выходом открытый коллектор.
Устройство и модуль должны иметь общую землю. Выход "открытый коллектор" подключите к клемме Dx.
Входы модуля гальванически развязаны от контроллера. Поэтому земли GND модуля и контроллера могут быть разными.
Изображения и чертежи устройства
По ссылкам ниже вы можете скачать изображения и чертежи устройства WBIO-DI-DR-8.
Corel Draw 2018: WBIO-DI-DR-8.cdr.zip
Corel Draw PDF: WBIO-DI-DR-8.cdr.pdf
Autocad 2013 DXF: WBIO-DI-DR-8.dxf.zip
Autocad PDF: WBIO-DI-DR-8.pdf