Версия от 20:38, 15 июля 2019; RomanKulibaba (обсуждение | вклад) (Новая страница: «The WBIO-AI-DV-12 module can also be connected via the interface Converter WB-MIO. Two device templates can be used: WBIO-AI-DV-12-50V and WBIO-AI-DV-1…»)
(разн.) ← Предыдущая | Текущая версия (разн.) | Следующая → (разн.)

The WBIO-AI-DV-12 module can also be connected via the interface Converter WB-MIO. Two device templates can be used: WBIO-AI-DV-12-50V and WBIO-AI-DV-12. If they are not in the Configurator, you need to update wb-mqtt-serial with apt-get update && apt-get install wb-mqtt-serial. The WBIO-AI-DV-12-50V template is designed for devices where jumpers are installed (voltage measurement on differential inputs in the range from 0 to 50 V), and the WBIO-AI-DV-12 template is for devices with removed jumpers (voltage measurement on differential inputs from 0 to 400 mV, on unipolar — from 0 to 2.5 V).