Parameter Value
"Power Supply"
Supply voltage 9 — 24 V DC
Power consumption
  • Idle mode (all relays switched off) — 0.10 W
  • All relays-0.5 W
  • Peak value (all relays are switched on simultaneously) — up to 2 W for 20 MS.
Terminals and wire section
Recommended wire cross-section with NSUI, mm2 0,75 — 1 (for plates screwless terminals), 1.5 a for relay outputs
Length of the standard sleeve NSVE, mm 8 (10 for adjusting screwless terminal blocks)
Torque of screws, N∙m 0,2 (for screw terminals), 0,4 — for relay outputs
Outputs
Number of outputs 2
Output type Mechanical relay contacts
Contact configuration Two-position

normally open (no version) or normally closed (NC version).

Output configuration Two groups (2 outputs per group)
Maximum switching voltage, AC 250 V
Maximum switching voltage, DC 30 Volts
Maximum switching current per channel
  • for resistive load — 7 A (for version NO), 3A (for NC)
  • for capacitive and inductive loads — 400 mA
Contact resistance < 100 milliohms
Voltage isolation between the controller and the output 1500 V (RMS value)
Lifetime: number of switches for load

7 A/230 V AC (resistive load)

100 000
Inputs
Number of inputs 2
Input type "Dry contact", not isolated from power supply
Functions
Control
Management interface RS-485
Interface isolation Uninsulated
Communication protocol Modbus RTU, address is set by software, factory settings are indicated on the label
RS-485 interface parameters set programmatically (see register card);
default: speed — 9600 bit/s; data — 8 bit; parity bit — none (N); stop bits — 2
Ready for operation after power supply ~0.1 c
dimensions
Overall dimensions (l x W x h) 52 x 24 x 20.5 mm
Display
Power and data exchange indication In older versions up to 2018g - Green status led under shrink tube

After 2018g - is missing.

Relay channel status indication no
operating Conditions
Air temperature
Relative humidity Up to 92%, no condensation